Industrial control systems
Passive industrial protocol evidence and its interpretation limits.
Protocol Support
S7Comm / S7CommPlus
TPKT/COTP TCP/102
Classic functions and visible Plus framing; not universal controller/model coverage
Modbus
TCP/502; explicitly configured RTU-over-TCP
Per-function requests/responses, correlation and loss markers
DNP3
TCP/20000
Link/application metadata, object headers and group-12 controls
CIP / ENIP
TCP/44818, UDP/2222
Supported encapsulation/services; inspect selected record type
OPCUA
TCP/4840
Supported visible framing/metadata; encryption limits payload interpretation
PROFINET
UDP/34964
Supported CM/DCE-RPC structures
BACnet/IP
UDP/47808
Supported service/object observations
IEC62351-related decoder
Registered TCP/2404
Selected recognized formats; the name does not promise complete IEC 60870/MMS coverage
Use net capture -overview for the installed inventory. A record type, a well-known port and a full protocol implementation are different claims.
Threat hunting
Collect both directions at an agreed observation point, preserve the original capture and inspect health before interpreting negative results. Analyze a copy; do not replay control messages to validate a passive finding.
S7 functions, workstation baseline and response limits
S7 hunt; internal/rules/examples/s7comm_hunt.yml
Modbus writes, banks/ranges and diagnostics
Modbus hunt; internal/rules/examples/modbus_hunt.yml
DNP3 controls, SBO and point mapping
DNP3 hunt; internal/rules/examples/dnp3_hunt.yml
Site-dependent examples require the site's approved initiators, point/register maps and maintenance policy. Rules and filtering explain typed expressions and local-time helpers.
Decoder selection off the standard port
The selector compares eligible parsers' evidence specificity; ascending registered port order only breaks ties. A weak registered-port signature can lose to stronger protocol evidence. Unknown-port UDP checks are datagram-aware; MQTT-SN's ambiguous short signature is restricted to its registered ports.
DNP3 Secure Authentication can be selected by dnp3 rather than iec62351 off-port because DNP3 validates its link CRC. Recognition does not establish cryptographic verification of Secure Authentication. See selector developer references for the implementation and confusable/reader regression tests.
Record timing and direction
Readers map a message's first captured byte to its timestamp and observed direction. Stream/transaction records can still be emitted only on completion or flush. Packet timestamps, decoder emission order and transaction orientation must not be treated as interchangeable; inspect each record's contract.
S7comm
Classic protocol ID 0x32 exposes function/message/error fields. Ack-Data ErrorClass == 0 && ErrorCode == 0 is header status only. Inspect item results, request/PDU reference and controller/process evidence before claiming success. For responses the initiator is the destination, not the PLC source address.
Plus protocol ID 0x72 exposes supported framing/opcodes. The decoder sets PayloadObscured; that is a visibility limitation, not proof that every version uses the same encryption/integrity scheme. The S7 guide records released-rule limitations separately from source corrections.
Modbus
The stream decoder distinguishes role, bank, zero-based wire address, quantity, values, exceptions and matched/unmatched/ambiguous responses. RTU endpoints need explicit -modbus-rtu-endpoints. Loss markers qualify missing coverage; a reply does not identify a user or independently prove a process effect. Follow the field-level Modbus guide.
DNP3
Header/data CRCs qualify framing, not authenticated identity. Point indexes need the outstation's device map. Group-12 control blocks are parsed; most other values are stepped over, not interpreted. A successful control response is distinct from independently observed equipment movement. See DNP3 limits and the v0.15.2 Class 0 correction.
CIP
This endpoint excerpt matches the released CIP schema. It is not a complete message definition:
ENIP
The corresponding released endpoint fields are direct fields, not the obsolete PacketContext Context = 9 from older docs:
Generate bindings from the tagged types/netcap.proto, never from partial documentation excerpts. make docs-check verifies excerpt field numbers/types against that schema.